Battery Runtime Calculator
To calculate battery runtime, multiply battery Amp-Hours by voltage to find nominal Watt-Hours, then multiply by usable Depth of Discharge (90% Lithium, 50% Lead-Acid) and inverter efficiency (90%). Divide net usable Watt-Hours by load wattage to obtain continuous autonomy hours.
Battery Load & Runtime Parameters
Peukert & DoD CalibratedHow to Calculate Battery Runtime with Peukert's Law & Inverter Losses
Sizing an off-grid solar or backup power battery bank requires moving beyond naive Watt-Hour math. Real-world runtime is governed by chemical kinetics, Depth of Discharge (DoD) thresholds, DC cable voltage drop, and high-discharge ampacity losses described by Peukert's Law:
Convert Amp-Hours to Usable Watt-Hours
Battery ratings in Amp-Hours are meaningless without nominal voltage. Multiply rated Ah by bank voltage (12V, 24V, or 48V). A 100Ah 12V battery provides 1,200Wh nominal. However, extracting 100% of this energy will instantly destroy lead-acid cells and trigger BMS low-voltage disconnect on lithium. Multiply nominal Wh by the safe DoD percentage (90% for LiFePO4 = 1,080Wh usable; 50% for AGM = 600Wh usable).
Account for DC-to-AC Inverter Conversion Loss
Inverters consume parasitic idle current (typically 15W to 40W just staying turned on) and experience 8% to 15% thermal conversion loss when stepping 12V DC up to 120V AC. Standard engineering practice dictates factoring in a 90% inverter efficiency multiplier (Usable Wh × 0.90) to prevent running out of power hours prematurely.
Apply Peukert's Law for Heavy Discharges
Lead-acid batteries are rated at a gentle 20-hour discharge rate (C/20). If you pull a heavy 50A load from a 100Ah lead-acid battery (a 2-hour discharge rate), internal resistance causes severe voltage collapse, reducing available capacity by up to 40%. Peukert's formula (t = H * (C/(I*H))^k) models this exponential loss. LiFePO4 batteries feature a nearly ideal k ≈ 1.05, suffering negligible capacity loss under heavy loads.
Size Heavy-Gauge DC Battery Cables
At low DC voltages, current is massive. A 1,200W coffee maker on a 12V system pulls over 110 Amps DC! Undersized cables cause high resistance, heating up wires and triggering premature inverter low-voltage cutoffs. Always use fine-stranded welding cable or UL-listed battery interconnect cables sized to NEC 310 ampacities with an inline Class T or ANL fuse.
Battery Chemistry Comparison: Lithium LiFePO4 vs Lead-Acid
| Battery Chemistry | Usable DoD | Peukert's k | Cycle Life (to 80%) | Weight per 100Ah | Thermal Runaway Risk |
|---|---|---|---|---|---|
| Lithium Iron Phosphate (LiFePO4) | 90% - 95% | 1.05 (Negligible) | 3,500 – 5,000 Cycles | ~25 lbs (Ultra-Light) | Zero (Thermally Stable) |
| Sealed AGM (Absorbent Glass Mat) | 50% Strict | 1.15 (Moderate) | 500 – 700 Cycles | ~65 lbs (Heavy) | Low (Sealed recombinant) |
| Flooded Lead-Acid (Deep Cycle) | 50% Strict | 1.25 (Severe Sag) | 400 – 600 Cycles | ~60 lbs (Heavy) | Off-gasses Hydrogen |
| Gel Cell Deep Cycle | 50% Strict | 1.18 (Moderate) | 700 – 900 Cycles | ~68 lbs (Heavy) | Low (Acid in silica gel) |
Battery Runtime & Capacity Frequently Asked Questions
How long will a 100Ah 12V battery run a 150W load? ▼
A 100Ah 12V Lithium LiFePO4 battery holds 1,200Wh nominal capacity. At 90% usable Depth of Discharge (1,080Wh) and factoring a 90% efficient pure sine wave inverter (972Wh usable), it will run a continuous 150W load for approximately 6 hours and 29 minutes. An AGM lead-acid battery of the same rating will only run for about 3 hours and 20 minutes due to 50% DoD limits and Peukert losses.
What is Peukert's Law and why does it reduce lead-acid runtime? ▼
Peukert's Law dictates that as the rate of battery discharge increases, the battery's available capacity decreases. For lead-acid chemistries (Peukert exponent k = 1.15 to 1.30), drawing high amperage causes rapid internal chemical starvation and voltage sag, shrinking a 100Ah battery to effectively 60Ah. Modern LiFePO4 lithium batteries have a Peukert exponent of ~1.05, maintaining full capacity even under heavy loads.
Why should deep-cycle lead-acid batteries never be discharged below 50%? ▼
Discharging lead-acid (flooded, AGM, or gel) batteries beyond 50% Depth of Discharge accelerates irreversible lead sulfate crystallization (sulfation) on the internal plates. Consistently draining a deep-cycle lead-acid battery to 80% DoD slashes its lifespan from 500-600 cycles down to fewer than 150 cycles, causing premature battery death.
How do I calculate DC current draw from an AC inverter load? ▼
Divide the AC load wattage by the product of DC nominal battery voltage and inverter efficiency: DC Amps = AC Watts / (DC Volts × Inverter Efficiency). For example, a 600W microwave running on a 12V battery with a 90% efficient inverter pulls 600 / (12 × 0.90) = 55.6 Amps DC.
Related Layout Tools
Solar Panel Tilt Angle Sizer
Fixed, winter, and summer solar tilt angles by latitude with roof pitch slope compensation.
Off-Grid Solar Daily Wh Estimator
Size solar arrays, daily watt-hour budgets, peak sun hours, and battery bank autonomy.
Amp Hours to Watt Hours Tool
Convert battery capacity from Ah to Wh across 12V, 24V, 48V with cell schematics.
Watt Hours to Amp Hours Tool
Convert stored energy from Wh and kWh to required Amp-Hours for battery bank sizing.