BlueprintCalcs 2D Parametric Trade Tools

Battery Runtime Calculator

To calculate battery runtime, multiply battery Amp-Hours by voltage to find nominal Watt-Hours, then multiply by usable Depth of Discharge (90% Lithium, 50% Lead-Acid) and inverter efficiency (90%). Divide net usable Watt-Hours by load wattage to obtain continuous autonomy hours.

BATTERY RUNTIME & DISCHARGE CAD SCHEMATIC
6h 29m Runtime • 0.97 kWh Usable
DETAIL A: DC CABLE & FUSING (3.5X) + - REC CABLE: #10 AWG Cu CLASS T FUSE: A • NEC 705.12: Continuous rating factor 125% • Max voltage drop limit: < 2.0% on DC run V Ah BANK 0.97 kWh % DoD Usable Lithium Iron Phosphate (LiFePO4) 13.9A LOAD & RUNTIME MONITOR 6.5h CONTINUOUS RUN Continuous Load: 150 Watts Inverter Efficiency: 90% C-Rate: C/0.1 DISCHARGE CALIBRATION: Peukert Exp: 1.05 | Nominal Wh: 1200 Wh | Usable: 972 Wh TOTAL ESTIMATED RUNTIME: 6h 29m Optimal discharge rate within manufacturer warranty limits. BANK: V Ah | DRAW: 13.9A DC | CABLE: #10 AWG Cu
✦ Runtime Benchmark: 6h 29m @ 150W Load
DC Draw: 13.9A Cable: #10 AWG Cu
Autonomy Time 6h 29m Continuous
Usable Energy 0.97 kWh Net
Current Draw 13.9A DC Conductor
Cable Gauge #10 AWG Cu NEC 310 Copper

Battery Load & Runtime Parameters

Peukert & DoD Calibrated
100 Ah
Small 20Ah to 600Ah Large Bank
150 Watts
20W (LEDs/CPAP) to 3000W (Heavy Appliances)
Battery Bank Takeoff & Cable Sizing 6h 29m
Total Nominal Wh:
1200 Wh
Net Usable Energy:
972 Wh (0.97 kWh)
DC Amps Draw:
13.9A DC
Discharge C-Rate:
0.14C
Recommended Cable:
#10 AWG Cu
Min Inverter Rating:
200W Pure Sine

How to Calculate Battery Runtime with Peukert's Law & Inverter Losses

Sizing an off-grid solar or backup power battery bank requires moving beyond naive Watt-Hour math. Real-world runtime is governed by chemical kinetics, Depth of Discharge (DoD) thresholds, DC cable voltage drop, and high-discharge ampacity losses described by Peukert's Law:

1

Convert Amp-Hours to Usable Watt-Hours

Battery ratings in Amp-Hours are meaningless without nominal voltage. Multiply rated Ah by bank voltage (12V, 24V, or 48V). A 100Ah 12V battery provides 1,200Wh nominal. However, extracting 100% of this energy will instantly destroy lead-acid cells and trigger BMS low-voltage disconnect on lithium. Multiply nominal Wh by the safe DoD percentage (90% for LiFePO4 = 1,080Wh usable; 50% for AGM = 600Wh usable).

2

Account for DC-to-AC Inverter Conversion Loss

Inverters consume parasitic idle current (typically 15W to 40W just staying turned on) and experience 8% to 15% thermal conversion loss when stepping 12V DC up to 120V AC. Standard engineering practice dictates factoring in a 90% inverter efficiency multiplier (Usable Wh × 0.90) to prevent running out of power hours prematurely.

3

Apply Peukert's Law for Heavy Discharges

Lead-acid batteries are rated at a gentle 20-hour discharge rate (C/20). If you pull a heavy 50A load from a 100Ah lead-acid battery (a 2-hour discharge rate), internal resistance causes severe voltage collapse, reducing available capacity by up to 40%. Peukert's formula (t = H * (C/(I*H))^k) models this exponential loss. LiFePO4 batteries feature a nearly ideal k ≈ 1.05, suffering negligible capacity loss under heavy loads.

4

Size Heavy-Gauge DC Battery Cables

At low DC voltages, current is massive. A 1,200W coffee maker on a 12V system pulls over 110 Amps DC! Undersized cables cause high resistance, heating up wires and triggering premature inverter low-voltage cutoffs. Always use fine-stranded welding cable or UL-listed battery interconnect cables sized to NEC 310 ampacities with an inline Class T or ANL fuse.

Battery Chemistry Comparison: Lithium LiFePO4 vs Lead-Acid

Battery Chemistry Usable DoD Peukert's k Cycle Life (to 80%) Weight per 100Ah Thermal Runaway Risk
Lithium Iron Phosphate (LiFePO4) 90% - 95% 1.05 (Negligible) 3,500 – 5,000 Cycles ~25 lbs (Ultra-Light) Zero (Thermally Stable)
Sealed AGM (Absorbent Glass Mat) 50% Strict 1.15 (Moderate) 500 – 700 Cycles ~65 lbs (Heavy) Low (Sealed recombinant)
Flooded Lead-Acid (Deep Cycle) 50% Strict 1.25 (Severe Sag) 400 – 600 Cycles ~60 lbs (Heavy) Off-gasses Hydrogen
Gel Cell Deep Cycle 50% Strict 1.18 (Moderate) 700 – 900 Cycles ~68 lbs (Heavy) Low (Acid in silica gel)

Battery Runtime & Capacity Frequently Asked Questions

How long will a 100Ah 12V battery run a 150W load? ▼

A 100Ah 12V Lithium LiFePO4 battery holds 1,200Wh nominal capacity. At 90% usable Depth of Discharge (1,080Wh) and factoring a 90% efficient pure sine wave inverter (972Wh usable), it will run a continuous 150W load for approximately 6 hours and 29 minutes. An AGM lead-acid battery of the same rating will only run for about 3 hours and 20 minutes due to 50% DoD limits and Peukert losses.

What is Peukert's Law and why does it reduce lead-acid runtime? ▼

Peukert's Law dictates that as the rate of battery discharge increases, the battery's available capacity decreases. For lead-acid chemistries (Peukert exponent k = 1.15 to 1.30), drawing high amperage causes rapid internal chemical starvation and voltage sag, shrinking a 100Ah battery to effectively 60Ah. Modern LiFePO4 lithium batteries have a Peukert exponent of ~1.05, maintaining full capacity even under heavy loads.

Why should deep-cycle lead-acid batteries never be discharged below 50%? ▼

Discharging lead-acid (flooded, AGM, or gel) batteries beyond 50% Depth of Discharge accelerates irreversible lead sulfate crystallization (sulfation) on the internal plates. Consistently draining a deep-cycle lead-acid battery to 80% DoD slashes its lifespan from 500-600 cycles down to fewer than 150 cycles, causing premature battery death.

How do I calculate DC current draw from an AC inverter load? ▼

Divide the AC load wattage by the product of DC nominal battery voltage and inverter efficiency: DC Amps = AC Watts / (DC Volts × Inverter Efficiency). For example, a 600W microwave running on a 12V battery with a 90% efficient inverter pulls 600 / (12 × 0.90) = 55.6 Amps DC.