Electrical Subpanel Wire Size Calculator

To size an electrical subpanel feeder, determine the panel amperage rating and one-way run distance. Cross-reference the 75°C column of NEC Table 310.16 for copper or aluminum ampacity, upsize conductors for voltage drops exceeding 3%, and isolate the neutral busbar from the chassis ground per NEC 250.32.

SUBPANEL 4-WIRE CAD SCHEMATIC
100A Subpanel • 1/0 AWG Aluminum
DETAIL A: FLOATING NEUTRAL BAR (3.5X) NEUTRAL BAR BOND SCREW REMOVED GROUND BAR (BONDED) NEC 250.32: 4-Wire Requirement • Neutral & Ground NEVER bonded at subpanel • Prevents circulating current on bare metal • EGC: #6 AWG Aluminum MAIN PANEL 100A 2-POLE FEEDER HOT 1 (L1) HOT 2 (L2) NEUTRAL (FLOATING) GROUND (EGC) 1/0 AWG Aluminum (1-1/4" to 1-1/2" PVC) 100A SUBPANEL LOAD CENTER MAIN LUGS (60 in-lbs) FLOATING NEUTRAL BONDED GROUND 2x 8FT GROUND RODS (6' APART) FEEDER RUN: 60 FT | VOLTAGE DROP: 1.93V (0.8%) • 4-Wire MHF (Mobile Home Feeder) Aluminum in Schedule 40 PVC HOT & NEUTRAL: 1/0 AWG Aluminum | GROUND EGC: #6 AWG Aluminum | TORQUE: 60 in-lbs
✦ NEC 310 Feeder: 100A Subpanel on 1/0 AWG Aluminum
Ground EGC: #6 AWG Aluminum Voltage Drop: 0.8%
Feeder Input Parameters 240V Split-Phase
100 Amps
60 Feet
10 ft 100 ft (Drop Threshold) 300 ft

* Detached structures mandate two 8ft ground rods spaced 6ft apart per NEC 250.32(A).

Contractor Feeder Takeoff & Specs NEC 310.16 Compliant
HOT & NEUTRAL (3 WIRES)
1/0 AWG Aluminum
EQUIPMENT GROUND (EGC)
#6 AWG Aluminum
MIN CONDUIT TRADE SIZE
1-1/4" to 1-1/2" PVC
VOLTAGE DROP (240V)
1.93V (0.8%)
⚡ Detached Structure GEC Requirement
#6 AWG Bare Solid Copper to Dual 8ft Ground Rods (6ft Spaced)
Recommended Assembly
4-Wire MHF (Mobile Home Feeder) Aluminum in Schedule 40 PVC

NEC Subpanel Sizing Rules: Sizing Conductors, Floating Neutrals, and Detached Building Grounding

Running an electrical subpanel to a workshop, finished basement, or detached garage requires precise adherence to NEC 2023 standards. An electrical subpanel is a distribution load center fed from a dedicated feeder breaker in the main service panel. Unlike a main service panel where neutral conductors and system bonding jumpers bond to earth ground, a subpanel operates under strict isolation rules per NEC 310.16 and NEC 250.32.

NEC Table 310.16 Subpanel Feeder Conductor Selection (75°C Terminals)

Subpanel Rating Copper Feeder (75°C) Aluminum Feeder (75°C) Min Cu EGC (NEC 250.122) Min Conduit Size
50 Amps #8 AWG Cu (50A) #6 AWG Al (50A) #10 AWG Cu 1 Inch
60 Amps #6 AWG Cu (65A) #4 AWG Al (65A) #10 AWG Cu 1 Inch
90 Amps #3 AWG Cu (100A) #1 AWG Al (100A) #8 AWG Cu 1-1/4 Inch
100 Amps #1 AWG Cu (130A) 1/0 AWG Al (120A) #8 AWG Cu 1-1/4 to 1-1/2 Inch
125 Amps 1/0 AWG Cu (150A) 2/0 AWG Al (135A) #6 AWG Cu 1-1/2 to 2 Inch
200 Amps 3/0 AWG Cu (200A) 250 kcmil Al (205A) #6 AWG Cu 2 to 2-1/2 Inch

The Floating Neutral Mandate: NEC 250.24(A)(5) and 250.32

The most common inspection snag on residential subpanels is failing to remove the green neutral bonding screw. In your main service panel, the utility neutral conductor and grounding electrodes bond together. In any downstream subpanel, the neutral busbar must float on plastic standoffs isolated from the metal cabinet.

Leaving the bonding strap in place turns equipment grounding conductors and the metal chassis into parallel neutral paths. Return currents flow through enclosures and conduit, creating dangerous shock hazards.

Detached Garages and Outbuildings: Dual Ground Rods (NEC 250.32)

When feeding power to a detached garage or pole barn, electricians must satisfy feeder grounding and electrode requirements:

  • Four-Wire Feeder: Two hots, one insulated neutral, and one equipment grounding conductor sized to NEC 250.122. Three-wire grandfathering is expired for modern work.
  • Grounding Electrodes: Install two 5/8-inch by 8-foot copper ground rods driven flush at least 6 feet apart per NEC 250.32(A).
  • GEC Connection: Connect the subpanel ground bar to ground rods using a continuous #6 AWG bare copper Grounding Electrode Conductor.

Copper vs. Aluminum Feeders: Cost and Physical Reality

For 100A and 200A subpanels, electricians routinely install 8000-series compact aluminum conductors such as 4-wire Mobile Home Feeder (MHF) or SER cable. A 100-foot run of 1/0 Aluminum costs roughly one-third of copper equivalents.

When terminating aluminum feeders, wire-brush strands, apply antioxidant paste, and torque lugs with a calibrated torque wrench to manufacturer specifications (typically 50 to 60 in-lbs for 100A lugs).

Feeder Voltage Drop Engineering Formula

NEC Informational Note 210.19(A) recommends keeping feeder voltage drop under 3% at full load. For single-phase 120/240V circuits:

V_drop = (2 × K × I × L) / C_M

Where K is 12.9 for copper and 21.2 for aluminum, I is design amperes, L is one-way run distance in feet, and C_M is circular mils. If drop exceeds 3.0%, upsize conductors.

Subpanel Feeder Wiring Frequently Asked Questions

What size wire do I need for a 100 amp subpanel? ▼

For a 100-amp subpanel within 60 feet, NEC Table 310.16 (75°C terminals) requires #1 AWG Copper or #1/0 AWG Aluminum. For runs over 70 feet, upsize to #2/0 AWG Aluminum or #1/0 AWG Copper to maintain voltage drop under 3% at 240V.

Why must the neutral and ground be separated in a subpanel? ▼

Under NEC 250.24(A)(5) and 250.32, bonding neutral and ground in a subpanel creates dangerous parallel paths for return neutral current across equipment chassis, metallic conduits, and plumbing, posing severe electrocution and fire hazards.

Does a detached garage subpanel require ground rods? ▼

Yes. NEC 250.32(A) mandates that any detached structure supplied by a feeder must have its own Grounding Electrode System, consisting of two 5/8-inch by 8-foot copper ground rods driven at least 6 feet apart connected via a #6 AWG bare copper GEC.

Can I use a 3-wire feeder to a detached garage subpanel? ▼

No. Since the 2008 National Electrical Code, 3-wire feeders to detached structures are prohibited for new construction. All subpanels require a 4-wire feeder: two hots, one insulated neutral, and one equipment grounding conductor (EGC).